Comet Labs 48-Port 10 Manual de usuario Pagina 63

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 76
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 62
Appendix
5.0 Electrical Specifications
Electrical and Mechanical specifications for the EX 5/7/11 RT.
5.1 System Input/Output Power Ratings
Table 5-1: EX 5/7/11 RT Voltages and Frequency Characteristics.
Source Voltage Frequency
Normal AC Source 156 to 280 VAC 40 to 70 Hz
Bypass AC Source 160 to 242 VAC* 58 to 62 Hz**
Load Output 200/208/220/230/240/250VAC 50/60 Hz autoranging
(120/208/240Vac (or frequency converter)
are possible with
transformer module)
(*): depends on output voltage setting, can be modified by software.
(**): set to +/- 4% by default, (1, 2, 4, 8% are possible values), can be modified by software.
5.2 System Overload Characteristics
Figure 5-1: Power Supplied as a Function of Input Voltage (Left), and Permissible UPS Overloads as a Function of
Time (Right).
1.02
0.5s
t
30s
1.1
1.25
1.5
60s 120s
Load Percentage
100%
70%
120V
U
160V 280V
Load Percentage
Appendix 5 — 186-86000-00 B01
Vista de pagina 62
1 2 ... 58 59 60 61 62 63 64 65 66 67 68 ... 75 76

Comentarios a estos manuales

Sin comentarios